TYPE: Pin type
CT Number: 3CT
Protections:
- Overcurrent
- Phase loss
- Motor disconnection
- Asymmetry
- Phase reversal (3PR)
Thermal adjustment (A): 1 ~ 5 / 4.4 ~ 22
Supply voltage: AC 100 ~ 260V
Frequency: 50/60Hz
Error receiver: Red/Green LED
Dimensions (mm): W x H x D 53 x 77.5 x 87.5
Installation: Directly on GMC relay
Compatible relays: GMC-9, GMC-12, GMC-18, GMC-22
Certifications: UL, CUL, CE
PROTECTION FUNCTIONS:
- Overcurrent: According to the inverse time characteristic curve.
- Phase loss: Disconnection within 3 sec when there is a phase loss greater than 70%. Note: In relays with 2CT, protection is provided only for 2 phases.
- Motor disconnection: According to the inverse time characteristic curve.
- Phase asymmetry: Within 5 sec for more than 50% phase loss.
- Phase reversal: Within 1 sec.
Certificates: RoHS, ISO 9001, ISO 14001, ISO 18001